beautypg.com

Explicit messaging – Rockwell Automation Ethernet Design Considerations Reference Manual User Manual

Page 92

background image

92

Rockwell Automation Publication ENET-RM002C-EN-P - May 2013

Chapter 5

Predict System Performance

Explicit Messaging

The RSView® and PanelView Plus messages are explicit messages. Reserve 10% of
the bandwidth of the EtherNet/IP communication module for explicit
messaging.

Explicit messaging throughput is also dependent upon network availability and
target availability. Therefore, reserving 10% of the total bandwidth does not
guarantee throughput.

Next determine if each EtherNet/IP communication module has enough
bandwidth to handle the implicit messaging.

EtherNet/IP
Interface

Total Bandwidth

10% Reserve for Explicit Messaging

1756-ENBT

5000 pps

500 pps

1756-EN2F
1756-EN2T
1756-EN2TR
1756-EN2TXT
1756-EN3TR

The pps for these modules depends on the
module’s series and firmware revision.
The modules support this pps:

Series A, firmware revision 2.x or earlier

= 10,000 pps

Series A or later, firmware revision 3.6 or

later= 25,000 pps

For more information on the pps supported
by these modules, see

Table 12 on page 66

.

One of the following:

Series A, firmware revision 2.x or earlier

= 1000 pps

Series A or later, firmware revision 3.6 or

later= 2500 pps

1768-ENBT

5000 pps

500 pps

1769-L23Ex

2000 pps

200 pps

1769-L32E
1769-L35E

4000 pps

400 pps

1769-L30ER

6000 pps

600 pps

1769-L30ERM

1769-L30ER-NSE

1769-L33ER

1769-L33ERM

1769-L36ERM

1769-L24ER-QB1B

1769-L24ER-QBFC1B

1769-L27ERM-QBFC1B

1769-L16ER-BB1B

1769-L18ER-BB1B

1769-L18ERM-BB1B

1788-ENBT

5000 pps

500 pps

1734-AENT

5000 pps

500 pps

1794-AENT

9500 pps

950 pps