Rockwell Automation MD65 User Manual Version 2.0 User Manual
Page 71

Parameter Descriptions
9-17
Sets the analog output signal mode (0-10 V, 0-20 mA, or 4-20 mA).
The output is used to provide a signal that is proportional to several
drive conditions.
Table 9.3 – A064 Options
A064 Option
Opto Out1 Logic
Opto Out2 Logic
0
NO (Normally Open)
NO (Normally Open)
1
NC (Normally Closed)
NO (Normally Open)
2
NO (Normally Open)
NC (Normally Closed)
3
NC (Normally Closed)
NC (Normally Closed)
A065 Analog Out Sel
Range:
0 to 20
Default:
0
See also:
A066, P035
Table 9.4 – Analog Output Signal Mode Selections
Option
Output
Range
Minimum
Output Value
Maximum Output Value
A066 (Analog Out High)
DIP
Switch
Position
0 = OutFreq 0-10
0-10 V
0 V = 0 Hz
P035 (Maximum Freq)
0-10 V
1 = OutCurr 0-10
0-10 V
0 V = 0 Amps
200% Drive Rated Output Current 0-10 V
2 = OutVolt 0-10
0-10 V
0 V = 0 Volts
120% Drive Rated Output Volts
0-10 V
3 = OutPowr 0-10
0-10 V
0 V = 0 kW
200% Drive Rated Power
0-10 V
4 = TstData 0-10
0-10 V
0 V = 0000
65535 (Hex FFFF)
0-10 V
5 = OutFreq 0-20
0-20 mA 0 mA = 0 Hz
P035 (Maximum Freq)
0-20 mA
6 = OutCurr 0-20
0-20 mA 0 mA = 0 Amps 200% Drive Rated Output Current 0-20 mA
7 = OutVolt 0-20
0-20 mA 0 mA = 0 Volts
120% Drive Rated Output Volts
0-20 mA
8 = OutPowr 0-20
0-20 mA 0 mA = 0 kW
200% Drive Rated Power
0-20 mA
9 = TstData 0-20
0-20 mA 0 mA = 0000
65535 (Hex FFFF)
0-20 mA
10 = OutFreq 4-20 4-20 mA 4 mA = 0 Hz
P035 (Maximum Freq)
0-20 mA
11 = OutCurr 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated Output Current 0-20 mA
12 = OutVolt 4-20
4-20 mA 4 mA = 0 Volts
120% Drive Rated Output Volts
0-20 mA
13 = OutPowr 4-20 4-20 mA 4 mA = 0 kW
200% Drive Rated Power
0-20 mA
14 = TstData 4-20 4-20 mA 4 mA = 0000
65535 (Hex FFFF)
0-20 mA
15 = OutTorq 0-10 0-10 V
0V = 0 Amps
200% Drive Related FLA
0-10 V
16 = OutTorq 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Related FLA
0-20 mA
17 = OutTorq 4-20 4-20 mA 4 mA = 0 Amp
200% Drive Related FLA
0-20 mA
18 = Setpnt 0-10
0-10 V
0V = 0%
100.0% Setpoint Setting
0-10 V
19 = Setpnt 0-20
0-20 mA 0 mA = 0%
100.0% Setpoint Setting
0-20 mA
20 = Setpnt 4-20
4-20 mA 4 mA = 0%
100.0% Setpoint Setting
0-20 mA