Technical Specifications
A-3
Protective Features
Motor Protection:
Programmable I
2
t overload protection provides Class
10 protection. See parameter P033.
Overcurrent:
200% hardware limit, 300% instantaneous fault
Over Voltage:
• 100-120 V AC Input – Trip occurs at 405 V DC bus
voltage (equivalent to 150 V AC incoming line
• 200-240 V AC Input – Trip occurs at 405 V DC bus
voltage (equivalent to 290 V AC incoming line)
• 380-460 V AC Input – Trip occurs at 810 V DC bus
voltage (equivalent to 575 V AC incoming line)
• 460-600 V AC Input – Trip occurs at 1005 V DC
bus voltage (equivalent to 711 V AC incoming line)
Under Voltage:
• 100-120 V AC Input – Trip occurs at 210 V DC bus
voltage (equivalent to 75 V AC incoming line)
• 200-240 V AC Input – Trip occurs at 210 V DC bus
voltage (equivalent to 150 V AC incoming line
• 380-480 V AC Input – Trip occurs at 390 V DC bus
voltage (equivalent to 275 V AC incoming line)
• 460-600 V AC Input –
•
If P042=3 “High Voltage” trip occurs at
487 V DC bus voltage (equivalent to
344 V AC incoming line)
•
If P042=2 “Low Voltage” trip occurs at
390 V DC bus voltage (equivalent to
275 V AC iincoming line)
Control Ride-
Through:
Minimum ride-through is 0.5 sec - typical value 2 sec
Faultless Power
Ride-Through:
100 milliseconds
Dynamic Braking
Internal brake IGBT included with all ratings 0.75 kW (1 HP) and larger.