MD65 AC Drive User Manual
6.5
Start and Speed Reference Control
The drive speed command can be obtained from a number of
different sources. The source is normally determined by P038
(Speed Reference). However, when A051 or A052 (Digital Inx
Select) is set to option 2, 4, 5, or 6, and the digital input is active,
A051 or A052 will override the speed reference commanded by
P038 (Speed Reference). See figure 6.2 for the override priority.
Figure 6.2 – Override Priority for the Speed Reference Command
Jog Input
Enabled and Active:
A051, A052, A053
or A054 = 2, 11, 12
No
Yes
No
Local/Remote Input
Enabled and Active:
(Digital Inx Sel) = 5
No
Yes
Drive Stopped
(Not Running)
Yes
Drive will Start and Run
at Jog Speed.
Direction comes from
I/O Terminal 03 Dir/Run REV
or
Jog Forward/Jog Reverse command
Start, Speed, and Direction commands
come from Integral Keypad.
Comm Select Input
Enabled and Active:
(Digital Inx Sel) = 6
No
Yes
Start, Speed and Direction commands
come from RS485 (DSI) port.
0-10V Override
Enabled and Active:
(Digital Inx Sel) = 13
No
Yes
Speed commands come from 0-10V.
Start and Direction
follows P036 (Start Source)
or
Bi-Polar input when enabled.
Speed commands come from 4-20mA.
Start and Direction
follows P036 (Start Source).
4-20mA Override
Enabled and Active:
(Digital Inx Sel) = 14
No
Yes
Run as specified by
A071-A077 (Preset Freq 1-7).
Start and Direction commands come
from P036 (Start Source).
A051/A052/A053
Preset Inputs Active
No
Yes
Run as specified by
A132 (PID Ref Select).
Start and Direction commands come
from P036 (Start Source).
PID Enabled:
A132 (PID Ref Select)
0
No
Run as specified by
P038 (Speed Reference).
Start and Direction commands come
from P036 (Start Source).
Yes