Parameter Descriptions
9-15
Important:
The value for A059 or A062 must be entered in
percent of drive rated output current.
7 = Above Cur: Drive exceeds the current (% Amps) value set in
Opto Outx Level (A059 or A062). Use A059 or A062 to set the
threshold.
Important:
Value for Opto Outx Level (A059 or A062) must be
entered in percent of drive rated output current.
8 = Above DCVolt: Drive exceeds the DC bus voltage value set in
Opto Outx Level (A059 or A062). Use A059 or A062 to set the
threshold.
9 = Retries Exst: The value set in Auto Rstrt Tries (A092) is
exceeded.
10 = Above Anlg V: The analog input voltage (I/O Terminal 13)
exceeds the value set in Relay Out Level (A056). Do not use if 10 V
Bipolar Enbl (A123) is set to 1 = Bi-Polar In.
11 = Logic In 1: An input is programmed as Logic In 1 and is active.
12 = Logic In 2: An input is programmed as Logic In 2 and is active.
13 = Logic 1 & 2: Both logic inputs are programmed and active.
14 = Logic 1 or 2: One or both logic inputs are programmed and
one or both is active.
15 = StpLogic Out: Drive enters StepLogic
TM
step with digit 3 of
the Command Word (A140-A147) set to enable the StepLogic
TM
output.
16 = Timer Out: The timer has reached the value set in Opto Outx
Level (A059 or A062). Use A059 or A062 to set the threshold.
17 = Counter Out: The counter has the reached the value set in
Opto Outx Level (A059 or A062). Use A059 or A062 to set the
threshold.
18 = Above PF Ang: The Power Factor angle has exceeded the
value set in Opto Outx Level (A059 or A062). Use A059 or A062 to
set the threshold.
19 = Anlg In Loss: An analog input loss has occurred. Program
Analog In Loss (A122) for action desired when input loss occurs.
20 = ParamControl: Enables the output to be controlled over
network communications by writing to Opto Outx Level (A059 to
A062). (0=Off, 1=On)