9-12
MD65 AC Drive User Manual
8 = Above DCVolt: Drive exceeds the DC bus voltage value set in
Relay Output Level (A056). Use A056 to set the threshold.
9 = Retries Exst: Number of retries set in Auto Rstrt Tries (A092) is
exhausted.
10 = Above Anlg V: The analog input voltage (I/O Terminal 13)
exceeds the value set in Relay Out Level (A056). Do not use if 10V
Bipolar Enbl (A123) is set to 1 = Bi-Polar In.
11 = Logic In 1: An input is programmed as Logic In 1 and is active.
12 = Logic In 2: An input is programmed as Logic In 2 and is active.
13 = Logic 1 & 2: Both logic inputs are programmed and active.
14 = Logic 1 or 2: One or both logic inputs are programmed and
one or both is active.
15 = StpLogic Out: Drive enters StepLogic
TM
step with digit 3 of
the Command Word (A140-A147) set to enable the StepLogic
TM
output.
16 = Timer Out: The timer has reach the value set in Relay Out
Level (A056). Use A056 to set the threshold.
17 = Counter Out: The counter has reached the value set in Relay
Out Level (A056). Use A056 to set the threshold.
18 = Above PF Ang: The Power Factor angle has exceeded the
value set in Relay Out Level (A056). Use A056 to set the threshold.
19 = Anlg In Loss: Analog input loss has occurred. Program
Analog In Loss (A122) for the desired action when input loss occurs.
20 = ParamControl: Enables the output to be controlled over
network communications by writing to Relay Out Level (A056).
0 = Off, 1 = On.
21 = NonRec Fault: Value set in Auto Rstrt Tries (A092) is
exceeded, Auto Rstrt Tries (A092) is not enabled, or a
non-resettable fault has occurred.
22 = EM Brk Cntrl: EM brake is energized. Program EM Brk Off
Delay (A160) and EM Brk On Delay (A161) for desired action.