Troubleshooting the PROFIBUS Module and Network
8-7
8.3
Viewing and Clearing Events
The module maintains an event queue that reports the history of its
actions. You can view the event queue using an LCD OIM or
VS Utilities software.
To View and Clear Events Using an LCD OIM
Use the procedure shown in figure 8.2 to access the event queue
using the LCD OIM. Note that you must have the RECOMM-PBUS
module as the selected device to access the event queue.
Events
Many events in the event queue occur under normal operation. If
you encounter unexpected communications problems, the events
may help you or Reliance Electric personnel troubleshoot the
problem. Table 8.5 lists events that may appear in the event queue.
Figure 8.2 – Viewing and Clearing Events Using an LCD OIM
Diagnostics:
Device Version
OIM Version
View Event Queue
P0: RECOMM-PBUS
Stopped Auto
Main Menu
Diagnostics
EvtQ# : E#xxxxx
Online @ 500kbps
1
Clrqu
Highlight Diagnostics icon
Highlight item
Monitor
Lang
>>
Press F2 key to
clear event queue
Table 8.5 – Event Codes and Descriptions
Code
Event
Description
1
No Event
Empty event queue entry.
2
DPI Bus Off Flt
A bus-off condition was detected on DPI. This
event may be caused by loose or broken
cables or by noise.
3
Ping Time Flt
A ping message was not received on DPI
within the specified time.
4
Port ID Flt
The module is not connected to a correct port
on a DPI product.
5
Port Change Flt
The DPI port changed.
6
Host Sent Reset
The DPI product issued this because it was
reset.
7
EEPROM Sum Flt
The EEPROM in the module is corrupt.