Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual
Page 59

Using I/O Messaging
6-7
Parameter Settings
Scanner Settings
An SST-PFB-SLC scanner is in slot 1 of the SLC rack and
configured as Station 0. The Advanced I/O Configuration is set up
as shown in figure 6.3.
The two PROFIBUS modules are set up as Station 1 and Station 2,
and are configured as 14 words input & output each. See chapter 5.
Table 6.1 – Parameter Settings for Sample SLC Program
Device
Parameter
Name
Value
Description
SP600
90
Speed Ref A Sel
22
‘DPI Port 5’ (RECOMM-PBUS)
300
Data In A1
140
Points to Accel Time 1 (140)
301
Data In A2
142
Points to Decel Time 1 (142)
302
Data In B1
100
Points to Jog Speed (100)
303
Data In B2
155
Points to Stop Mode A (155)
304
Data In C1
101
Points to Preset Speed 1 (101)
305
Data In C2
102
Points to Preset Speed 2 (102)
306
Data In D1
103
Points to Preset Speed 3 (103)
307
Data In D2
104
Points to Preset Speed 4 (104)
310
Data Out A1
140
Points to Accel Time 1 (140)
311
Data Out A2
142
Points to Decel Time 1 (142)
312
Data Out B1
100
Points to Jog Speed (100)
313
Data Out B2
155
Points to Stop Mode A (155)
314
Data Out C1
101
Points to Preset Speed 1 (101)
315
Data Out C2
102
Points to Preset Speed 2 (102)
316
Data Out D1
103
Points to Preset Speed 3 (103)
317
Data Out D2
104
Points to Preset Speed 4 (104)
RECOMM-PBUS
11
DPI I/O Config
xxx1 1111
Enables Cmd/Ref, Datalinks A-D
Figure 6.3 – Advanced I/O Configuration