Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 94

background image

8-4

PROFIBUS Communications Module

8.1.3 NET A Status Indicator

Table 8.3 – NET A Status Indicator: State Definitions

Status

Cause

Corrective Actions

Off

The module is not
powered or is not
connected properly
to the network.

Securely connect the module to
the drive using the Internal
Interface cable and to the
network using a PROFIBUS
cable.

Correctly connect the
PROFIBUS cable to the
PROFIBUS connector.

Apply power to the drive.

Flashing
Red

Error in PROFIBUS
configuration.

Re-configure the PROFIBUS
module.

Solid
Red

Error in PROFIBUS
controller
initialization.

Cycle power to the drive.

Re-configure the PROFIBUS
scanner.

Solid
Green

The module is
properly connected
and communicating
on the network.

No action required.