Starting Up the Drive for Vector Regulation
2-1
C
HAPTER
2
Starting Up the Drive
for Vector Regulation
This chapter describes the basic start-up procedure for drives which utilize flux vector
control (FVC) or sensorless vector control (SVC). Part of this procedure describes
how to select vector regulation.
If you are starting up a drive which will perform V/Hz regulation, refer to the V/Hz
start-up procedure in chapter 1 instead. Do not perform the start-up procedure in this
chapter.
The start-up procedure below provides step-by-step instructions for:
•
powering up
•
checking monitor mode displays
•
accessing program mode
•
configuring General parameters (designated with a "P")
•
configuring specific vector parameters (designated with a "U")
•
checking motor rotation direction
•
running the drive
This start-up procedure describes how to program the minimum set of parameters that
usually need to be programmed for applications using vector regulation. Once you
program these parameters, their values are retained even if power is lost. You only
need to re-program them if you want to change how the drive operates.
Your application may require programming other parameters in addition to the ones
described in this start-up procedure. Refer to chapter 4 for a description of all the
parameters to verify whether you need to program any additional parameters as well.
Appendix A provides a list of parameters listed alphabetically.
Throughout this manual, you will see references to parameter names and the
numbers that identify them for the drive. This manual uses the same format that will be
shown on the keypad/display to refer to parameters:
P.nnn
U.nnn
H.nnn
r.nnn
where: nnn is a number
P designates General parameters
U designates Vector parameters
H designates Volts/Hertz parameters
r designates optional RMI parameters