Rockwell Automation GV3000/SE AC Gen. Purpose & Vector Bookshelf Drive Start-Up and Reference Manual User Manual
Page 202
E-2
GV3000/SE AC Bookshelf Drive Software Reference, Version 6.06
Second Menu General Parameters (Continued)
❶
: Parameter default is Power Module-dependent
*See parameter description in chapter 4
Parameter
No.
Parameter Name
USA
(P.049 = USA)
EUROPE
(P.049 = EUr)
JAPAN
(P.049 = JPn)
P.028
Speed Display Scaling P.048 = U-H
P.048 = UEC
*
U.017
*
U.017
*
U.017
P.029
Elapsed Time Meter
Read only
Read only
Read only
P.030
Elapsed Time Meter Reset
OFF
OFF
OFF
P.031
Preset Speed 1
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.032
Preset Speed 2
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.033
Preset Speed 3
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.034
Preset Speed 4
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.035
Preset Speed 5
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.036
Preset Speed 6
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.037
Preset Speed 7
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.038
Preset Speed 8
P.048 = U-H
P.048 = UEC
5.0 Hz
150 RPM
5.0 Hz
150 RPM
5.0 Hz
150 RPM
P.039
Encoder Loss Enable
OFF
OFF
OFF
P.040
Motor Overload Enable
ON
ON
ON
P.041
Motor Overload Type
FC
FC
FC
P.042
Line Dip Ride-Through Time
5.0
5.0
5.0
P.043
Fault Auto Reset Attempts
0
0
0
P.044
Fault Auto Reset Time
8
8
8
P.045
Output Phase Loss Enable
ON
ON
ON
P.047
Carrier Frequency (kHz)
❶
❶
❶
P.048
V/Hz or Vector Regulation
U-H
U-H
U-H
P.049
Country Defaults
USA
EUr
JPn
P.050
Restore Defaults
OFF
OFF
OFF
P.051
Programming Disable
0
0
0
P.052
AUTO/MAN Key Disable
OFF
ON
OFF
P.053
Manual Reference Preset Enable
OFF
OFF
OFF
P.054
Level Sense Start Enable
OFF
OFF
OFF
P.055
STOP/RESET Key Disable
OFF
OFF
OFF
P.060
Network Drop Number
1
1
1
P.061
Network Connection Type
0
1
0
P.062
Option Port: Communication Loss Response
0
0
0