GV3000/SE AC Bookshelf Drive Software Reference, Version 6.06

P.031 to P.038 Preset Speed 1 through Preset Speed 8

(continued)

Each speed is selected using external switches connected to terminals 17, 18, and 19
on the Regulator board.

The presets may also be selected using the Remote Meter Interface (RMI) board. If
you have installed an optional RMI board in your drive, refer to Appendix F and the
RMI board instruction manual (D2-3341) for more information.

The presets can also be selected as the OCL reference using P.064 (Option Port:
Network Trim Reference Source). See Appendix H for more information about the
OCL.

Table 4.4 – Preset Speed Digital Inputs

Digital Inputs (Terminals)

Selected

Speed Reference

8 (17)

7 (18)

6 (19)

0 (open)

0 (open)

0 (open)

P.031 or analog input (see P.008,

selections 5, 6, and 7)

0 (open)

0 (open)

1 (closed)

P.032

0 (open)

1 (closed)

0 (open)

P.033

0 (open)

1 (closed)

1 (closed)

P.034

1 (closed)

0 (open)

0 (open)

P.035

1 (closed)

0 (open)

1 (closed)

P.036

1 (closed)

1 (closed)

0 (open)

P.037

1 (closed

1 (closed)

1 (closed)

P.038