Programming Reference
4-17
In selections 5, 6, and 7, a digital input will initiate the selected preset speed which will
override the analog speed reference. Refer to table 4.4 in the P.031 parameter
description.
The selection is dependent upon what is selected for parameter P.007 (Terminal Strip
Digital Inputs Configure). The selection made in P.007 determines what the remaining
free digital inputs are used for. See table 4.3 for acceptable combinations.
P.008 Terminal Strip Speed Reference Source
This parameter
selects the source of
the terminal strip
speed reference.
The terminal strip
speed reference is
used when:
•
the terminal strip is
the selected control
source (P.000 = rE)
or
•
the local keypad or
serial port is the
selected control
source (P.000 =
LOCL or SErL) and
AUTO is selected
(AUTO LED is on).
Parameter Range:
0 = Analog reference. (Digital inputs 6, 7, and 8 are
not used. See P.007.)
1 = MOP selection. (Uses terminal strip digital input
6 for MOP increment and digital input 7 for the
MOP decrement function. Digital input 8 is not
used.)
2 = Two (2) preset speeds. (Uses terminal strip
digital input 6. Digital inputs 7 and 8 are not
used.)
3 = Four (4) preset speeds. (Uses terminal strip
digital inputs 6 and 7. Digital input 8 is not used.)
4 = Eight (8) preset speeds. (Uses all terminal strip
digital inputs.)
5 = Analog reference and one (1) preset speed.
(Uses terminal strip digital input 6. Digital inputs
7 and 8 are not used.)
6 = Analog reference and three (3) preset speeds.
(Uses terminal strip digital inputs 6 and 7. Digital
input 8 is not used.)
7 = Analog reference and seven (7) preset speeds.
(Uses terminal strip digital inputs 6, 7, and 8.)
Default Setting:
0
Parameter Type:
Configurable
Refer also to parameters:
P.007 Terminal Strip Digital Inputs Configure
P.031 Preset Speed 1
r.030 Digital Input Configuration