Many events in the event queue occur under normal operation. If
you encounter unexpected communications problems, the events
may help you or Reliance Electric personnel troubleshoot the
problem. Table 8.7 lists events that may appear in the event queue.
Table 8.7 – Event Codes and Descriptions
Code
Event
Description
1
No Event
Empty event queue entry.
2
DPI Bus Off Flt A bus-off condition was detected on DPI. This
event may be caused by loose or broken cables or
by noise.
3
Ping Time Flt
A ping message was not received on DPI within
the specified time.
4
Port ID Flt
The module is not connected to a correct port on a
DPI product.
5
Port Change
Flt
The DPI port changed.
6
Host Sent
Reset
The DPI product issued this because it was reset.
7
EEPROM Sum
Flt
The EEPROM in the module is corrupt.
8
Online @
125kbps
The module and DPI product are communicating
at 125kbps.
9
Online @
500kbps
The module and DPI product are communicating
at 500kbps.
10
Bad Host Flt
The module was connected to an incompatible
product.
11
Dup. Port Flt
Another peripheral with the same port number is
already in use.
12
Type 0 Login
The module has logged in for type 0 control.
13
Type 0 Time Flt The module has not received a type 0 status
message within the specified time.
14
DL Login
The module has logged into a Datalink.
15
DL Reject Flt
The host rejected an attempt to log in to a Datalink
because the Datalink is not supported or is used
by another peripheral.
16
DL Time Flt
The module has not received a Datalink message
within the specified time.
17
Control
Disabled
The module has sent a “Soft Control Disable”
command to the DPI product.
18
Control
Enabled
The module has sent a “Soft Control Enable”
command to the DPI product.