3 configuring the network using cmd software – Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual
Page 33
Configuring the Interbus Scanner
5-3
PIDD and PODD parameters are used to identify what will be
transmitted on the network and the amount of network I/O the CMD
software will allocate on the scanner.
5.3
Configuring the Network Using CMD
Software
Before starting the network configuration process, make sure the
PC running CMD software is connected to the SST scanner (a null
modem cable is supplied with the scanner). The SLC and drives
need to be connected to the Interbus network and powered in order
for CMD software to configure the network. The CMD software tool
automatically creates a Reliance Electric sub-folder (in the Slaves
folder), if it does not already exist.
CMD needs to be in Extended Mode to configure the network. A
password (supplied by Phoenix Contact along with the CMD
software), is requested for this functionality each time CMD is
started. After CMD has started, you can also click Options/
Extended (Function Scope) to enter the password.
Step 1.
Select File / New from the pull-down menu to create a
new project. (See figure 5.2.)
28
PIDD W4 Cfg
12198
2FA6
Datalink B1 Out
30
PIDD W5 Cfg
12199
2FA7
Datalink B2 Out
32
PIDD W6 Cfg
12200
2FA8
Datalink C1 Out
34
PIDD W7 Cfg
12201
2FA9
Datalink C2 Out
36
PIDD W8 Cfg
12202
2FAA
Datalink D1 Out
38
PODD W0 Cfg
12184
2F98
Logic Command
40
PODD W1 Cfg
12185
2F99
Reference
42
PODD W2 Cfg
12188
2F9C
Datalink A1 In
44
PODD W3 Cfg
12189
2F9D
Datalink A2 In
46
PODD W4 Cfg
12190
2F9E
Datalink B1 In
48
PODD W5 Cfg
12191
2F9F
Datalink B2 In
50
PODD W6 Cfg
12192
2FA0
Datalink C1 In
52
PODD W7 Cfg
12193
2FA1
Datalink C2 In
54
PODD W8 Cfg
12194
2FA2
Datalink D1 In
Table 5.1 – Module Parameter Settings for Ladder Example (Continued)
Parameter
Name
Value
Description
Binary/
Decimal
Hexadecimal