Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual
Page 68

7-8
Interbus Communications Module
In the example ladder logic program, the user would load these
registers before calling the subroutine to perform the PCP Read:
Figure 7.4 – Reading Fault 1 Time (244) from an SP600 Drive (DPI Host)
Echo of the Command Word (PCP Read)
Message
Command word = 4 = PCP Read (bit 2 ON)
N22:10
Command
4
4
SLC Addr
ess
D
es
cr
iption
Va
lu
e
(H
ex)
N22:22
N22:13
N22:12
N22:11
N22:23
Reply
12532
2
4
-32,764
0
2
5
CR# = 2 (Station 1.0)
Sub Index not used
Number of words following = 5
CR# =2(Station 1.0)
30F4
2
4
2
5
N22:21
0
8004
Va
lu
e
(D
ec
)
N22:20
Result = 0 (success)
N22:25
N22:26
0
59
4
Number of bytes read = 4
3B235B hex = 3875675 decimal = 387.5675 hours
0
3B
4
N22:24
N22:27 9051
235B
"8000" (bit 15 ON) indicates Reply message present
Status word:
"0004" (bit 2 ON) echo's the command (PCP Read)
3001h is the start of PowerFlex 70 parameters (Pr.1)
Index =3000h+F4h = Parameter 244 [Fault 1 Time]
F4 hex = 244 dec = Parameter 244 [Fault 1Time]
Index = 3000h + F4h = Fault 1 Time (244)
3001h is the start of SP600 parameters (1)
F4 hex = 244 dec = Fault 1 Time (244)
0 = SP600 (DPI Host)
0 = SP600 (DPI Host)
Message
CR# =2 (Station 1.0)
N22:0
Request
2
2
SLC Addr
ess
D
es
cr
iption
Va
lu
e
(H
ex)
N22:1
0
0= PowerFlex 70 (DPI Host)
0
Va
lu
e
(D
ec
)
N22:3
244
F4
Parameter # = 244 [Fault 1 Time]
0 = SP600 (DPI Host)
Parameter # = 244 (Fault 1 Time)