Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual
Page 40
5-10
Interbus Communications Module
The mapping in the scanner is set up in bytes. Inputs to the scanner
start at byte #512 and outputs start at byte #0.
PIDD/PODD parameter settings in the module determine the length
of I/O data mapped. In the example, each device is configured for 9
words (144 bits) of inputs and 9 words (144 bits) of outputs, the
maximum allowed for each device.
Using the PIDD/PODD values previously set in the RECOMM-IBUS
module, the I/O layout in the scanner is as shown in table 5.2.
Device 1.0’s SLC addressing is as follows:
Device 2.0’s SLC addressing starts immediately after 1.0
addressing (I:1.9 and O:1.9).
Table 5.2 – Scanner I/O Layout
Word
Inputs
(Data to Master)
Station
Outputs
(Data from
Master)
Station
1.0
2.0
1.0
2.0
0
Logic Status
512
530
Logic Command
0
18
1
Feedback
514
532
Reference
2
20
2
Datalink A1 Out
516
534
Datalink A1 In
4
22
3
Datalink A2 Out
518
536
Datalink A2 In
6
24
4
Datalink B1 Out
520
538
Datalink B1 In
8
26
5
Datalink B2 Out
522
540
Datalink B2 In
10
28
6
Datalink C1 Out
524
542
Datalink C1 In
12
30
7
Datalink C2 Out
526
544
Datalink C2 In
14
32
8
Datalink D1 Out
528
546
Datalink D1 In
16
34
Table 5.3 – SLC Addressing for Device 1.0
Word
Inputs
(Data to
Master)
Assignment
Outputs
(Data from
Master)
Assignment
Scanner SLC
Scanner SLC
0
Logic Status
512
I:1.0 Logic
Command
0
O:1.0
1
Feedback
514
I:1.1 Reference
2
O:1.1
2
Datalink A1 Out
516
I:1.2 Datalink A1 In
4
O:1.2
3
Datalink A2 Out
518
I:1.3 Datalink A2 In
6
O:1.3
4
Datalink B1 Out
520
I:1.4 Datalink B1 In
8
O:1.4
5
Datalink B2 Out
522
I:1.5 Datalink B2 In
10
O:1.5
6
Datalink C1 Out
524
I:1.6 Datalink C1 In
12
O:1.6
7
Datalink C2 Out
526
I:1.7 Datalink C2 In
14
O:1.7
8
Datalink D1 Out
528
I:1.8 Datalink D1 In
16
O:1.8