Add the kinetix, 350 drive to the, Rslogix 5000 – Rockwell Automation Logix5000 Control System: Connect Kinetix 350 Drives over an EtherNet/IP Network Quick Start User Manual

Page 34: Project

background image

34

Rockwell Automation Publication IASIMP-QS032A-EN-P - March 2012

Chapter 2 Add a Kinetix 350 Drive to an RSLogix 5000 Project

Add the Kinetix 350 Drive to the RSLogix 5000 Project

1.

Verify that the 2097-V31PR2-LM drive is not powered at the IPD connector nor the
BP connector.

2.

Verify the following about your RSLogix 5000 project:

The project is offline.

The controller is configured such that Time Synchronization is enabled.

The Enable Time Synchronization feature is on the Date/Time tab of the Controller
Properties dialog box.

3.

Verify the Logix5000 controller
mode switch is in the PROG
mode position.

4.

Right-click your network port and
choose New Module.

IMPORTANT

The tasks described in this section use an RSLogix 5000 project for a CompactLogix 5370 L3 controller.
CompactLogix 5370 L3 controllers require that you use RSLogix 5000, version 20.00.00 or later.

If you are using a different Logix5000 controller, your project’s RSLogix 5000 software version requirement might
be different.

RUN

REM

PROG