Rockwell Automation 20B PowerFlex 70 / 700 Parameters FRN 3.xx User Manual
Page 4
Par
Parameter Name
Factory Default
Programmed Value
Par
Parameter Name
Factory Default
Programmed Value
101
Preset Speed 1
5.0 Hz
195
MOP Rate
1.0 Hz/s
102
Preset Speed 2
10.0 Hz
196
Param Access Lvl
Basic
103
Preset Speed 3
20.0 Hz
197
Reset To Defalts
Ready
104
Preset Speed 4
30.0 Hz
198
Load Frm Usr Set
Ready
105
Preset Speed 5
40.0 Hz
199
Save To User Set
Ready
106
Preset Speed 6
50.0 Hz
200
Reset Meters
Ready
107
Preset Speed 7
60.0 Hz
201
Language
Not Selected
117
Trim In Select
Analog In 2
202
Voltage Class
Based on Drive Cat. No.
118
Trim Out Select
xxxxxxxxxxxxxx00
203
Drive Checksum
Read Only
119
Trim Hi
60.0 Hz
209
Drive Status 1
Read Only
120
Trim Lo
0.0 Hz
210
Drive Status 2
Read Only
121
Slip RPM @ FLA
Based on
[Motor NP RPM]
211
Drive Alarm 1
Read Only
122
Slip Comp Gain
40.0
212
Drive Alarm 2
Read Only
123
Slip RPM Meter
Read Only
213
Speed Ref Source
Read Only
124
PI Configuration
xxxxxxxxxx000000
214
Start Inhibits
Read Only
125
PI Control
xxxxxxxxxxxxx000
215
Last Stop Source
Read Only
126
PI Reference Sel
PI Setpoint
216
Dig In Status
Read Only
127
PI Setpoint
50.00%
217
Dig Out Status
Read Only
128
PI Feedback Sel
Analog In 2
218
Drive Temp
Read Only
129
PI Integral Time
2.00 Secs
219
Drive OL Count
Read Only
130
PI Prop Gain
1.00
220
Motor OL Count
Read Only
131
PI Lower Limit
-[Maximum Freq]
224
Fault Frequency
Read Only
132
PI Upper Limit
+[Maximum Freq]
225
Fault Amps
Read Only
133
PI Preload
0.0 Hz
226
Fault Bus Volts
Read Only
134
PI Status
Read Only
227
Status 1 @ Fault
Read Only
135
PI Ref Meter
Read Only
228
Status 2 @ Fault
Read Only
136
PI Fdback Meter
Read Only
229
Alarm 1 @ Fault
Read Only
137
PI Error Meter
Read Only
230
Alarm 2 @ Fault
Read Only
138
PI Output Meter
Read Only
234
Testpoint 1 Sel
499
140
Accel Time 1
10.0 Secs
235
Testpoint 1 Data
Read Only
141
Accel Time 2
10.0 Secs
236
Testpoint 2 Sel
499
142
Decel Time 1
10.0 Secs
237
Testpoint 2 Data
Read Only
143
Decel Time 2
10.0 Secs
238
Fault Config 1
xxxxxxxxx1001x10
146
S-Curve %
0%
240
Fault Clear
Ready
147
Current Lmt Sel
Cur Lim Val
241
Fault Clear Mode
Enabled
148
Current Lmt Val
[Rated Amps] x 1.5
242
Power Up Marker
Read Only
149
Current Lmt Gain
250
243
Fault 1 Code
Read Only
150
Drive OL Mode
Both-PWM 1st
244
Fault 1 Time
Read Only
151
PWM Frequency
4 kHz
245
Fault 2 Code
Read Only
155
Stop Mode A
Ramp
246
Fault 2 Time
Read Only
156
Stop Mode B
Coast
247
Fault 3 Code
Read Only
157
DC Brk Lvl Sel
DC Brake Lvl
248
Fault 3 Time
Read Only
158
DC Brake Level
[Rated Amps]
249
Fault 4 Code
Read Only
159
DC Brake Time
0.0 sec
250
Fault 4 Time
Read Only
160
Bus Reg Ki
450
259
Alarm Config 1
xxxxxx111x111111
161
Bus Reg Mode A
Adjust Freq
270
DPI Baud Rate
125 kbps
162
Bus Reg Mode B
Both-Frq 1st
271
Drive Logic Rslt
Read Only
163
DB Resistor Type
Internal Res
272
Drive Ref Rslt
Read Only
168
Start At PowerUp
Disabled
273
Drive Ramp Rslt
Read Only
169
Flying Start En
Disabled
276
Logic Mask
xxxxxxxxxx1x1111
170
Flying StartGain
4000
277
Start Mask
xxxxxxxxxx1x1111
174
Auto Rstrt Tries
0
278
Jog Mask
xxxxxxxxxx1x1111
175
Auto Rstrt Delay
1.0 Secs
279
Direction Mask
xxxxxxxxxx1x1111
184
Power Loss Mode
Coast
280
Reference Mask
xxxxxxxxxx1x1111
185
Power Loss Time
0.5 Secs
281
Accel Mask
xxxxxxxxxx1x1111
190
Direction Mode
Unipolar
282
Decel Mask
xxxxxxxxxx1x1111
192
Save HIM Ref
xxxxxxxxxxxxxxx1
283
Fault Clr Mask
xxxxxxxxxx1x1111
193
Man Ref Preload
Disabled
284
MOP Mask
xxxxxxxxxx1x1111
194
Save MOP Ref
xxxxxxxxxxxxxx00
285
Local Mask
xxxxxxxxxx1x1111