Rockwell Automation 20B PowerFlex 70 / 700 Parameters FRN 3.xx User Manual
Page 18
![background image](/manuals/580976/18/background.png)
PowerFlex 70 Parameter Record
Machine #
Date programmed
Drive Serial #
Par
Parameter Name
Minimum Value
Maximum Value
Factory Default
Programmed Value
324
Analog In 1 Loss
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Goto Preset1
Hold OutFreq
325
Analog In 2 Hi
4.000 mA
20.000 mA
10.0 Volt
-10.0 V
+10.0 V
0.0
10.0 V
326
Analog In 2 Lo
4.000 mA
20.000 mA
0.0 Volt
-10.0V
+10.0V
0.0V
10.0V
327
Analog In 2 Loss
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Goto Preset1
Hold OutFreq
341
Anlg Out Absolut
Analog Out1
1
342
Analog Out1 Sel
Output Freq
Output Freq
Command Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Outout
%Motor OL
%Drive OL
343
Analog Out1 Hi
0.00 Volt
10.00 Volt
10.00 Volt
344
Analog Out1 Lo
0.00 Volt
10.00 Volt
0.00 Volt
361
Digital In1 Sel
Not Used
Stop - CF
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
PI Reset
13 of 17