2 related hardware and software – Rockwell Automation 57C332 AutoMax Power Supply Module and Racks User Manual
Page 8
1Ć2
D Other instruction manuals applicable to your hardware
configuration
D Your personal computer and DOSoperating system manual(s).
1.2
Related Hardware and Software
The Power Supply modules and Racks are sold individually.
M/NĂ57C493 contains one 376 watt Power Supply module and two
keyswitch keys. M/N 57C494 contains one 147 watt Power Supply
module and two keyswitch keys. M/N 57C331 contains one 16Ćslot
Rack. M/N 57C332 contains one 10Ćslot Rack. M/N 57C334 contains
one 6Ćslot Rack. One Power Supply module and one Rack are used
with various input, output, and special purpose modules, as well as
the following hardware and software, which can be purchased
separately:
1. AutoMax or DCS5000 Processor modules. The following
Processor modules can be used only with the M/N 57C493
Power Supply module:M/NĂ57C430 AutoMax Processor(s) or
M/NĂ57C407 DCS5000 Processor(s). Note that all Processors in
a single Rack must be of the same type, i.e., AutoMax and DCS
5000 Processors cannot be mixed in one Rack.
D M/N 57C430 AutoMax Processor
D M/N 57C407 DCS5000 Processor
Note that all Processors in a single rack must be of the same
type, i.e., AutoMax and DCS5000 Processors cannot be mixed in
the same rack.
The following AutoMax Processors can be used with the M/N
57C493 or M/N 57C494 Power Supply module. These processor
modules can be mixed in the same rack:
D M/N 57C430A
D M/N 57C431
D M/N 57C435
2. ReSource AutoMax Programming Executive software or
ReSource DCS 5000 Programming Executive software.
3. M/NĂ57C127 RSĆ232C ReSource Interface Cable. This cable is
used to connect the personal computer to the Processor module.
4. M/NĂ57C413 (or later) or M/N 57C423 (or later) Common Memory
module. This module is used when there is more than one
Processor in the Rack. Note that only M/N 57C413B (and later) or
M/N 57C423 (and later) Common Memory module can be used
with the M/N 57C494 Power Supply.
5. M/N 57C492 Battery BackĆUp. This unit is used when there is a
Common Memory module (M/N 57C413 or M/N 57C413A only),
a M/N 57C407 or M/N 57C430 Processor, or both in the Rack.
The Battery BackĆUp unit can be used only with the M/N 57C493
Power Supply.
6. M/N 57C384 Battery BackĆUp cable. This cable is used with the
Battery BackĆUp unit.