Rockwell Automation 57C332 AutoMax Power Supply Module and Racks User Manual

Page 23

background image

3Ć7

Take all of the modules out of the Rack, being careful not

to touch the connectors on the back.

Step 4.

Loosen the bolts that hold the rack to panel approximately

1/8"-1/4". Lift the Rack slightly while holding it against the

panel until both top bolts are positioned in the larger bolt

holes and the lower two bolts have cleared the smaller

holes. Pull the Rack away from the panel and set aside.

Step 5.

Position the replacement Rack against the panel at a slight

angle so that the bottom is a few inches away from the

panel. Place the Rack against the panel so that the upper

two bolts are visible through the larger part of the bolt

holes at the top of the Rack.
Carefully slide the Rack down so that the bolts are

wedged in the top (smaller) area of the bolt holes, while at

the same time moving the lower portion of the Rack

toward the cabinet or panel onto the lower bolts. The

lower bolts should be firmly wedged against the upper

edge of the lower bolt holes on the Rack. Tighten all the

bolts.

Step 6.

Insert the Power Supply module into the leftmost and

widest slot in the Rack. Use a screwdriver to attach the

module to the Rack.

Step 7.

If you are using the Battery BackĆUp unit, plug one end of

the Battery BackĆUp cable into the Power Supply module

faceplate connector labeled BATTERY BACK UP". Plug

the other end into the Battery BackĆUp unit. Rotate the

keyswitch on the front panel from Memory Protect to the

Program postion.

Step 8.

Insert the Processor module(s) and other modules. Use a

screwdriver to attach the modules to the Rack.

Step 9.

Use a screwdriver to attach the connectors to their mating

halves on the appropriate modules.

Step 10. Connect 115 VAC power to the Rack following the

instructions below.

CAUTION: Do not connect incoming AC power directly to the power supply module

faceplate.Connectpowertothecorrectterminalsontherackonly.Failuretoobservethis

precaution could result in damage to or destruction of the equipment.

a) Make certain that there is an unbroken path from the

cabinet to the plant ground.

b) Connect incoming AC power to the Rack as follows:

Rack Terminal Label

Input

189

120 VAC

188

120 VAC + (hot)

Cover the incoming wire ends with a Fastont

connector and attach them securely to the appropriate

terminals using a screwdriver.

c) Connect the power and ground wires from the Rack to

the Power Supply module as follows: