3.0 INSTALLATION

This section describes how to install and replace the Power Supply

module and Rack.

DANGER

THE USER IS RESPONSIBLE FOR CONFORMING WITH ALL APPLICABLE

LOCAL, NATIONAL, AND INTERNATIONAL CODES. WIRING PRACTICES,

GROUNDING, DISCONNECTS, AND OVERĆCURRENT PROTECTION ARE OF

PARTICULAR IMPORTANCE. FAILURE TO OBSERVE THIS PRECAUTION

COULD RESULT IN SEVERE BODILYINJURYOR LOSS OF LIFE.

CAUTION: This equipment must be connected to a power source for which it was

designed. Verify that the available power is 115 volts. Failure to observe this precaution

could result in damage to equipment.

3.1

Wiring

To reduce the possibility of electrical noise interfering with the proper

operation of the control system, exercise care when installing the

wiring between the system and the external devices. For detailed

recommendations refer to IEEE 518.
The external wiring to the modules in the Rack must be carefully

routed to minimize electrical noise and crosstalk between input and

output wiring. Group and bundle wire types by similar electrical

signals, being especially careful to separate lowĆ and highĆlevel

control signals and AC and DC wiring.
If the 115 VAC input signal is subject to severe harmonic distortion,

install a constant voltage transformer on the line.

3.2

Initial Installation

CAUTION: Thecabinetorpanelonwhichtherackismountedmustbelocatedinanarea

away from or shielded from sources of EMI, such as radar beams and transmission

towers. Failure to observe this precaution could result in damage to or destruction of the

equipment.

CAUTION: Air flow around the rack must be sufficient to dissipate the heat generated by

all of the hardware in and around the rack. Allow at least two inches of clearance on each

side of the rack. Avoid placing large, heatĆgenerating equipment underneath the rack

fans. Additional userĆsupplied fan cooling or air conditioning is required if the ambient

temperature exceeds 60_C. Failure to observe this precaution could result in damage to

or destruction of the equipment.