Technical Specifications

Power Supply Module (M/N 57C494)

Ambient Conditions

D Storage temperature:

-40

o

C Ć 85

o

C

D Operating temperature:

0_C Ć 60_C

D Humidity:

5-90% nonĆcondensing

D Altitude:

operation from sea level at 60

o

C to 10,000 feet (3048 meters)

with linear derating of 1

o

C per 1000 feet above 5000 feet.

Dimensions

D Height:

29.8 cm

11

3

/

4

inches

D Width:

7.1 cm

ă2

13

/

16

inches

D Depth:

19.7 cm

ă7

3

/

4

inches

D Weight:

ă2.6 kg

5

3

/

4

lbs

System Power Requirements

D Input voltage:

nominal 100/120 VAC, 85Ć132 VAC acceptable

range

D Current:

2.6 Amp at 120 VAC

D Frequency:

nominal 50/60 Hz, 47Ć63 Hz acceptable range

D Protection:

5 Amp 250 VAC MDA time delay fuse

D Fault current limit:

10,000 Amps

D Maximum source rating: 50KVA

DC Output

D +5 VDC at 20 amps

D +/-12 VDC at 1 amp

D +/-15 VDC at 0.75 amp

D Maximum continuous output power: ă147 Watts

D +5 VDC output holdup time: 3 msec. minimum after loss of AC input at

full load and minimum input line voltage

D Input line loss: capable of a 1 cycle 60 Hz line loss at nominal input

line voltage

Regulation

D Nominal +5 VDC:

-2.5% to +3% regulation

D Nominal +/- 12 VDC:

+/-10% regulation

D Nominal +/- 15 VDC:

+/- 1% regulation

Efficiency

D 65% minimum at nominal line voltage and full load

Isolation

D 1500 VDC input to output

D 700 VDC output to chassis

Protection

D Overvoltage:

+5V

5.6V+/-0.15V

+/-12V

14.4V +/-0.6V

+/-15V

16.5V +/-0.5V