beautypg.com

Rockwell Automation 57C332 AutoMax Power Supply Module and Racks User Manual

Page 20

background image

3Ć4

a) Ground the cabinet or panel on which the Rack will be

mounted. Make certain that there is an unbroken path

from the cabinet to the plant ground (earth).

b) Ground the rack with a ground wire connected to one

of the protective ground terminals provided on each

side of the rack. The ground wire color and size must

be in accordance with appropriate international and

national standards and codes.

c) Connect incoming AC power to the Rack as follows:

Rack Terminal Label

Input

189

120 VAC

188

120 VAC + (hot)

Cover the incoming wire ends with a Fastont

connector and attach them securely to the appropriate

terminals using a screwdriver.

d) Connect the power and ground wires from the Rack to

the Power Supply module as follows:

Wire Color

Wire Label

Power Supply

Faceplate Connector

black

L2

L2

orange

L1

L1

green

-

GND

The wires labeled L2 and L1 should remain twisted

together as much as possible between the Rack and

the Power Supply module.

Step 8.

Using a screwdriver, reĆattach the nameplate bracket to

the base of the rack.

Step 9.

Turn on power to the system.

DANGER

THE POWER SUPPLYMODULE OPERATES USING AC INPUT VOLTAGE

CAPABLE OF PRODUCING SEVERE SHOCK. MAKE CERTAIN THAT THE

EXTERNAL AC SUPPLYCIRCUIT IS TURNED OFF BEFORE INSERTING OR

REMOVING THE MODULE OR ANYCONNECTING CABLES. FAILURE TO

OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILYINJURYOR

LOSS OF LIFE.

Step 10. Verify the installation by connecting the personal computer

to the port labeled PROGRAMMER/PORT B" on the

leftmost Processor in the Rack and running the ReSource

programming software. Try to read from or write to the

registers on each of the modules in the Rack.