Publication 2707-UM005B-EN-P - July 2000
6-2 Installing the MicroView Operator Interface
Agency Certifications
The MicroView Operator Interface now has the following agency
certifications: CSA Class 1 Division 2 Hazardous Location, UL Class 1
Division 2 Hazardous Location. It also has CE certification. This
equipment is suitable for use in Class 1, Division 2, Groups A, B, C,
and D or non-hazardous locations only.
Hazardous Locations
When used in a hazardous environment, the ultimate enclosure must
be in accordance with Class 1, Division 2 wiring methods as described
in the National Electrical Code (ANSI/NFPA 70) and the Canadian
Electrical Code.
All peripheral equipment must be suitable for the location in which it
is used.
Use only a Class 2 power source as described in the National Electrical
Code (ANSI/NFPA 70) and the Canadian Electrical Code. The
recommended AC to DC adapters (2707-PS120, 2707-PS220) meet this
requirement.
The MicroView module contains no user serviceable parts.
European Union Directive
Compliance
If this product is installed within the European Union or EFTA regions,
the following regulations apply.
This apparatus is tested to meet Council Directive 89/336
Electromagnetic Compatibility (EMC) Standards:
•
EN50081-1 Class (Residential) Emissions
•
EN50082-2 Class A (Industrial) Immunity
ATTENTION
!
USE ONLY WITH CLASS 2 POWER SOURCE
LIMITED TO 30 VDC OPEN CIRCUIT AND 8A
SHORT CIRCUIT.
UTILISER AVEC UNE TENSION D’ALIMENTATION
CLASSE 2 DE 30 VCC MAXI EN CIRCUIT OUVERT
AVEC UN COURANT DE COURT-CIRCUIT DE 8A
MAXI.
ATTENTION
!
EXPLOSION HAZARD: DO NOT CONNECT OR
DISCONNECT EQUIPMENT WHILE CIRCUIT IS
LIVE UNLESS AREA IS KNOWN TO BE NON–
HAZARDOUS.
RISQUE D’EXPLOSION: NE PAS BRANCHER OU
DEBRANCHER TANT QUE LE CIRCUIT EST SOUS
TENSION, A MOINS QU’IL NE S’AGISSE D’UN
EMPLACEMENT NON DANGEREUX.