22 Fiber Optic Cable Installation and Handling Instructions
Publication 2090-IN010C-EN-P – April 2005
Message Instruction Settings
The Message Configuration Screen has three tabs: Configuration,
Communication and Tag. This is where you set the values for the test.
Figure 15 Message Configuration Tab
Enter the following values for the fields on the Configuration Tab screen.
Message Type: CIP generic
Service Type: Custom
Service Code: 51 hex.
Class: 315 hex.
Instance: 0
Attribute: 0.
Source Element: The Source Element must be an INT array of 1. The
first element of the array needs to be set to the value of the desired test
mode.
Servicecode[0] = Value set to desired Physical testmode