Example 1 - 8 terminal bases, 8 modules – Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual
Page 51

3–17
Communicating with FLEX I/O Modules
Publication 1794ĆUM009D-EN-P - April 2004
•
smallest rack size is 1/4, regardless of the mode switch settings
Some examples of rack definition are shown below.
Adapter
= 1 Logical Rack in Standard mode, any density or analog module mix
Module
Module
Module
Module
Example 1 - 8 Terminal Bases, 8 Modules
= 1/4 Rack in Compact mode with 8Ćpt modules; 1/2 Rack in Compact mode (with 16Ćpt modules)
Module
Module
Module
Module
= 2 Logical Racks in Standard 32 mode, any density or analog module mix
PrimaryĆ
Adapter
= 1 Logical Rack in Complementary mode (16 16Ćpt modules), primary input modules - complement
output modules and vice versa; analog complemented with another analog module or an empty slot
= 1/2 Rack in Complementary mode (16 8Ćpt modules), primary input modules - complement output
modules and vice versa; analog complemented with an empty slot
Module
Module
Module
Module
Example 2 - 16 Terminal Bases, 16 Modules, Complementary Mode
Module
Module
Module
Module
Complement
Adapter
Module
Module
Module
Module
Module
Module
Module
Module
= 2 Logical Racks in Complementary 32 mode (16 modules total, any density),
Last
M d l
Rack Size for each Addressing Mode
Module
Position
Standard
32
Standard Compact
16
Compact
8
Complement
32
Complement
16
Complement 8
0
1/4 rack
1/4 rack
1/4 rack
1/4 rack
1/4 rack
1/4 rack
1/4 rack
1
1/2 rack
1/4 rack
1/4 rack
1/4 rack
1/2 rack
1/4 rack
1/4 rack
2
3/4 rack
1/2 rack
1/4 rack
1/4 rack
3/4 rack
1/2 rack
1/4 rack
3
Full rack
1/2 rack
1/4 rack
1/4 rack
Full rack
1/2 rack
1/4 rack
4
1-1/4 rack
3/4 rack
1/2 rack
1/4 rack
1-1/4 rack
3/4 rack
1/2 rack
5
1-1/2 rack
3/4 rack
1/2 rack
1/4 rack
1-1/2 rack
3/4 rack
1/2 rack
6
1-3/4 rack
Full rack
1/2 rack
1/4 rack
1-3/4 rack
Full rack
1/2 rack
7
2 Full racks Full rack
1/2 rack
1/4 rack
2 Full racks
Full rack
1/2 rack