Module Calibration

Chapter 7

7Ć7

is, you want to subtract 47 counts from your input data. The lower byte
remains 00 during offset calibration.

5. Repeat above steps for channels 2 through 6 respectively.

6. Apply the values by sending a BTW to the module.

Gain Calibration

1. Connect the 402.00, .01% resistors to the swing arm as shown in

Figure 7.2.

2. Place the module in platinum ohm mode. This provides 30 mohm

resolution display.

3. Examine word 3 of the read block transfer data file. It should be around

13400 decimal. Your actual value will be a percentage of 13400.

For example, if the data in word 3 is 13408, then:
(13400–13408)/134000 = –0.000597.
Your actual data value differs from the theoretical value (at 402.0 ohms
input resistance) by –0.000597, or –0.0597%.

You can compensate for this error by entering the percentage difference in
binary coded fraction form. Table 7.D lists the value for bits 7–0.

Table 7.D

Value for Bits 7 through 0

Bit

Value

Bit 07

Sign bit

Bit 06

= 0.0976562%

Bit 05

= 0.0488281%

Bit 04

= 0.024414%

Bit 03

= 0.012207%

Bit 02

= 0.00610351%

Bit 01

= 0.00305175%

Bit 00

= 0.00152587%