beautypg.com

Default configuration for the rtd input module, Chapter summary – Rockwell Automation 1771-IR , D17716.5.76 RTD INPUT MODULE User Manual

Page 30

background image

Module Configuration

Chapter 5

5Ć6

Word

Description

Bits

1.5

0

1

1

1

1

Word 1 (cont.)

2.0

1

0

1

0

0

2.5

1

1

0

0

1

3.0

1

1

1

1

0

Word 2

If bit 10 is set in word 1, and temperature readings are desired, word

2 must also be used. Enter the exact resistance of 10 ohm RTD at

25

o

C in BCD. Range is 9.00 to 11.00 ohms. Values less than 9.00

ohms or greater than 11.00 ohms will default to 10.00 ohms.

Non-BCD values will also default to 10.00 ohms.

Words 3-8

Individual channel bias words entered in BCD. This value is

subtracted from the channel data in the BTR. The bias value is

always a positive number. Bias value range is 0

Words 9-14

Individual channel calibration words.

Word 15

Auto-calibration request word - used to automatically calibrate

selected channels and save the calibration constants in EEPROM.

Bit 00

Offset calibration complete

Bit 01

Gain calibration complete

Bit 02

Save complete

Bit 06

EEPROM fault

Bit 07

Faulty calibration (no save)

Bits 10-15

Channel failed calibration

If zeroes are written to the module in all configuration positions, the module
will default to:

BCD

format

100 ohm platinum RTD

temperature in degrees C

real time sampling = inhibited (sample time = 50msec)

In this chapter you learned how to configure your module’s hardware, condition
your inputs and enter your data.

Default Configuration for the

RTD Input Module

Chapter Summary