beautypg.com

Module calibration chapter 7 – Rockwell Automation 1771-IR , D17716.5.76 RTD INPUT MODULE User Manual

Page 37

background image

Module Calibration

Chapter 7

7Ć4

Figure 7.2

Resistor Location for Gain Calibration

18

16

14

12

10

8

6

4

2

C

B

A
C

B

A
C

B

A
C

B

A
C

B

A
C

B

A

12935

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Terminal

Identification

402.0 ohm Resistor

Repeat for

each channel

2. Apply power to the module.

3. After the connections stabilize, request the gain calibration by setting bit

01 in BTW word 15 and sending a block transfer write (BTW) to the
module. Refer to Table 7.A.

NOTE: Normally, all channels are calibrated simultaneously (bits 10–15 of
word 15 are octal 0). To disable calibration on any channel, set (1) the
corresponding bit 10 through 15 of word 15.

4. Queue BTRs to monitor for gain calibration complete and channels which

may not have calibrated successfully.