Library of Routines 6-3
OC_CloseScanner
This function must always be called before exiting the application.
Syntax:
int
OC_CloseScanner(HANDLE handle);
Parameters:
Description:
This function releases control of the scanner device, releases the
interrupt assigned by OC_OpenScanner, and disables the segment
address assignment.
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Example:
HANDLE
Handle;
int
retcode;
retcode = OC_CloseScanner( Handle );
Parameter:
Description:
handle
Must be a valid handle returned from OC_OpenScanner
ATTENTION
!
The system might become unstable if you don’t call
OC_CloseScanner before exiting the application.
Name:
Value:
Description:
SUCCESS
0
scanner was closed successfully
ERR_OCACCESS
2
handle
does not have access to the scanner