Oc_clearfault, Oc_clearfault -2, Example – Rockwell Automation 1747-PCIS API Software - Open Controller User Manual
Page 62: Syntax, Parameters: description, Return value: considerations

Publication 1747-UM002A-US-P - June 2000
6-2 Library of Routines
Example:
BYTE
buffer[100];
WORD
buffer_crc;
int
retcode;
retcode = OC_CalculateCRC( buffer, 100, &buffer_crc );
OC_ClearFault
OC_ClearFault clears any fault condition of the scanner.
Syntax:
int
OC_ClearFault(HANDLE handle);
Parameters:
Description:
All extended error information must be retrieved before the fault can
be cleared.
If the scanner encounters an error condition, it generates an extended
error and faults. The fault forces the scanner into Idle mode. The
scanner cannot be placed into Scan mode until the fault is cleared.
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Example:
HANDLE
Handle;
int
retcode;
retcode = OC_ClearFault( Handle );
Parameter:
Description:
handle
Must be a valid handle returned from OC_OpenScanner
Name:
Value:
Description:
SUCCESS
0
fault was cleared successfully
ERR_OCACCESS
2
handle
does not have access to the scanner
ERR_OCEXTERR
11
scanner extended error message, see OC_GetExtendedError
ERR_OCINIT
5
scanner has not been initialized, see OC_InitScanner
ERR_OCRESPONSE
10
scanner did not respond to request