Error Codes A-3
The error code data provides information specific to the cause of all
extended errors, except 0xF0. The first byte of the error code data
contains a subsystem identifier with the following information:
The second byte of the error code data provides details about the
subsystem identifier with the following information:
0x60 - 0x8F
Module specific errors (see I/O module documentation)
0x90
MINT occurred on disabled slot
0x91
PINT occurred on disabled slot
0x93
Unsupported module error
0x94
Module has been inserted or reset
0xF0
Internal scanner error
Subsystem ID:
Description:
0x06
Scanner Communications
0x08
Backplane Interface (module I/O)
Error Code:
Description:
0x00
Download error - invalid directory file pointer block
0x01
Download error - change to Idle mode failed
0x02
Download error - configuration file CRC failed (byte 1
contains the file number)
0x03
Download error - directory CRC failed
0x04
Download error - input or output image exceeds partition
allocation (byte 1 contains 0 for output image, 1 for input)
Extended Error
Code:
Description: