Panel mounting – Rockwell Automation 1769-OF8V CompactLogix Analog Output Module User Manual
Page 9
CompactLogix Analog Output Module 9
Rockwell Automation Publication 1769-IN089A-EN-P - March 2011
Maintain spacing from enclosure walls, wireways, and adjacent equipment.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Panel Mounting
Mount the module to a panel by using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
Panel Mounting Using Modules as a Template
The following procedure lets you use the assembled modules as a template for
drilling holes in the panel. If you have sophisticated panel mounting equipment,
you can use the dimensional template provided on page 9. Due to module
mounting hole tolerance, it is important to follow this procedure.
1.
On a clean work surface, assemble no more than three modules.
2.
Using the assembled modules as a template, carefully mark the center of
all module-mounting holes on the panel.
3.
Return the assembled modules to the clean work surface, including any
previously mounted modules.
4.
Drill and tap the mounting holes for the recommended M4 or #8 screw.
Host
Compact I/
O
Compact I/O
Compact I/
O
End
Cap
132 (5.197)
122.6±0.2
35
(1.38)
28.5
(1.12)
Refer to host controller documentation for this dimension.
For more than 2 modules: (number of modules-1) X 35mm (1.38 in.)
NOTE: All dimensions are in
mm (in.). Hole spacing
tolerance: ±0.4 mm (0.016 in.)