beautypg.com

Compactlogix analog output module 33 – Rockwell Automation 1769-OF8V CompactLogix Analog Output Module User Manual

Page 33

background image

CompactLogix Analog Output Module 33

Rockwell Automation Publication 1769-IN089A-EN-P - March 2011

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged
Shock)

20 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged
Shock)

30 g

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)

5…95% noncondensing

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2

4 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

±1 kV line-earth(CM) on shielded ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80
MHz

Supply power and current ratings

Backplane (1769-OF8C):

5V DC, 145mA

24V DC, 185 mA

Backplane (1769-OF8V):

5V DC, 145mA

24V DC, 135 mA

Field (1769-OF8C):

0…20 mA

4…20 mA

Field (1769-OF8V):

-10V to… +10V, 0…+5V, 0…+10V, 1 to… +5V

Isolation voltage

30V (continuous), Reinforced Insulation Type, channel to
system and channel to channel.
Type tested at 710V DC for 60 s

Environmental Specifications 1769-OF8C and 1769-OF8V

Attribute

1769-OF8C and 1769-OF8V

This manual is related to the following products: