CompactLogix Analog Output Module 19

Rockwell Automation Publication 1769-IN089A-EN-P - March 2011

PF = Analog power fail.

S = General status (over-range, under-range, or open-circuit).

D = Open-circuit diagnostics.

H = Output held bit.

U = Under-range (or low-clamp exceeded) alarm.

O = Over-range (or high-clamp exceeded) alarm

Configuration Data File

The manipulation of the bits from this file is normally done with programming
software, such as RSLogix 500, RSNetWorx for DeviceNet software, during
initial configuration of the system. In that case, graphical screens are provided by
the programmer to simplify configuration. However, some devices, like the
1769-ADN DeviceNet adapter, also allow the bits to be altered as part of the
control program, using communication rungs. In that case, it is necessary to
understand the bit arrangement. The channel configuration words, the first two
words of each eight word group, are described on

page 21

. Refer to the

CompactLogix I/O Analog Modules User Manual, publication

1769-UM002

,

for additional details.

IMPORTANT

The output module’s input data file reflects the analog output data echo
of the module, not necessarily the electrical state of the output terminals.
It does not reflect shorted or open outputs.

Word

Description

Word

Description

0

Channel 0 Configuration Word 0

24

Channel 3 Configuration Word 0

1

Channel 0 Configuration Word 1

25

Channel 3 Configuration Word 1

2

Channel 0 Fault Value Word

26

Channel 3 Fault Value Word

3

Channel 0 Program Idle Mode Word

27

Channel 3 Program Idle Mode Word

4

Channel 0 Low Clamp

28

Channel 3 Low Clamp

5

Channel 0 High Clamp

29

Channel 3 High Clamp

6

Channel 0 Ramp Rate

30

Channel 3 Ramp Rate