CompactLogix Analog Output Module 21

Rockwell Automation Publication 1769-IN089A-EN-P - March 2011

E = Channel Enable: (0 = Disabled, 1 = output 0 and hold Enabled,
process changes)

Reserved = Set to zero

SIU = System interrupt low clamp, under-range alarms: (0 = Disabled, 1
= Enabled)

SIO = System interrupt high clamp, over-range alarms: (0 = Disabled, 1
= Enabled)

LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled, 1
= Enabled)

ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by
fault states.)

FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)

PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)

HI = Hold for initialization: (0 = Disabled, 1 = Enabled)

PFE = Program/idle to fault enable: (0 = Disabled, 1 = Enabled)

Channel Configuration Words

The first two words of each eight-word group in the configuration file let you
change the parameters of each channel independently. For example, words 8 and
9 correspond to channel 1 while words 56 and 57 correspond to channel 7.

Word/Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Word 0

E

Reserved

SIU

SIO

LA

ER

FM

PM

HI

PFE

Word 1

Reserved

Output Data
Format Select

Reserved

Output
Type/Range

Define

Indicate this

These bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Program (idle)
to Fault Enable

Program (Idle)
Mode Data
Applied

(1)

0

0

0

0

0

0

0

0

0

Fault Mode Data
Applied

(1)

0

0

0

0

0

0

0

0

1

Hold for
Initialization

Disabled

0

0

0

0

0

0

0

0

0

Enabled

0

0

0

0

0

0

0

0

1