Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 89
Publication 1734-UM008B-EN-P - August 2005
1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-27
Program Fault Note
Programming Fault Error bit - If an incomplete, incorrect, or
conflicting set of configuration parameters are sent to the module, the
Program Fault bit will be asserted and an error code will be placed in
the Programming error Code word (assembly 6816). The module will
not enter a normal operational state. Bit definitions (decimal) for the
error codes are:
10
An invalid assembly was chosen for poll consumption (0, 105 or
106
are
valid).
9
The decimal point position is outside of the acceptable range.
8
Counter 0 window ON & OFF values are equal and not zero OR
Counter 0 window ON & OFF value is greater than the Rollover.
7
A tie has been connected to an unprogrammed window.
6
A configuration was selected that requires the scalar and none
was
programmed
OR
Multiple scalars were selected.
5
The preset is out of range (Rollover).
4
A rollover of zero was programmed through PWM was not
selected
OR
A rollover was programmed and PWM was selected OR
Rollover is out of range (>0x01000000).
3
A configuration requiring a time base was selected and no gate
interval was set OR
Gate interval is out of range (>200) OR
Product of time base and gate interval is greater than 3 seconds.
2
A time base was entered that is not a multiple of 10 OR
Time base is out of range (>3000, i.e., 3 seconds).
1
ZF/BF/AF were selected and no filter was programmed OR
Multiple filters were selected.
0
A reserved configuration/mode was programmed.