1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-5

Filter Time Note

To enter Filter values from +32,768 to +65,535

µs, use this conversion

formula:

Desired Filter Value (in

µs) - 65536 = Entered Filter Value (in

µs).
Example: For a 40ms filter time, 40000 - 65536 = -25536

Discrete 2 POINT Output –
Without Diagnostic Status

1734-OA2
2 POINT 120V AC Output
1734-OW2
2 POINT AC/DC Relay Output
1734-OX2
2 POINT Relay Output N.O./N.C.

Configuration Data

Data Type

Default
Value

Valid Data Values

Fault Mode - POINT 0, 1

SINT, BIT

0

0=Fault Value
1=Hold Last State

Fault Value - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Program Mode - POINT 0, 1

SINT, BIT

0

0=Program Value
1=Hold Last State

Program Value - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Input Data

Data Type

Default
Value

Valid Data Values

None

Output Data

Data Type

Default
Value

Valid Data Values

Output Data - POINT 0, 1

SINT, BIT

0

0=Off
1=On