Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual
Page 74
![background image](/manuals/579831/74/background.png)
Publication 1734-UM008B-EN-P - August 2005
A-12 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
1734-IE2V
2 Channel Analog Voltage Input
Configuration Data
Data Type
Default
Value
Valid Data Values
Low Engineering Channel 0
INT
0
-32,768 to 32,767
High Engineering Channel 0
INT
10,000
-32,768 to 32,767
Digital Filter Channel 0
INT
0
0 to 10,000 ms
Low Alarm Limit Channel 0
INT
500
-32,768 to 32,767
High Alarm Limit Channel 0
INT
9,500
-32,768 to 32,767
Low Low Alarm Limit Channel 0
INT
200
-32,768 to 32,767
High High Alarm Limit Channel 0
INT
9,800
-32,768 to 32,767
Range Type Channel 0
SINT
2
0=-10 to +10V
2=0 to 10V
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Low Engineering Channel 1
INT
0
-32,768 to 32,767
High Engineering Channel 1
INT
10,000
-32,768 to 32,767
Digital Filter Channel 1
INT
0
0 to 10,000 ms
Low Alarm Limit Channel 1
INT
500
-32,768 to 32,767
High Alarm Limit Channel 1
INT
9,500
-32,768 to 32,767
Low Low Alarm Limit Channel 1
INT
200
-32,768 to 32,767
High High Alarm Limit Channel 1
INT
9,800
-32,768 to 32,767
Range Type Channel 1
SINT
2
0=-10 to +10V
2=0 to 10V
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Notch Filter (Channel 0 & 1)
SINT
2
1=50Hz
2=60Hz
4=250Hz
6=500Hz
Real Time Sample (Channel 0 & 1)
INT
100
0 to 10,000 ms