1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-19
Analog 2 Channel Output
1734-OE2C
2 Channel Analog Current Output
Configuration Data
Data Type
Default
Value
Valid Data Values
Fault Value Channel 0
INT
0
-32,768 to 32,767
Program Value Channel 0
INT
0
-32,768 to 32,767
Low Engineering Channel 0
INT
1,638
-32,768 to 32,767
High Engineering Channel 0
INT
8,191
-32,768 to 32,767
Low Limit Channel 0
INT
-32,768
-32,768 to 32,767
High Limit Channel 0
INT
32,767
-32,768 to 32,767
Range Type Channel 0
SINT
0
0=4-20mA
2=0-20mA
Fault Mode Channel 0
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Idle Mode Channel 0
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Fault Value Channel 1
INT
0
-32,768 to 32,767
Program Value Channel 1
INT
0
-32,768 to 32,767
Low Engineering Channel 1
INT
1,638
-32,768 to 32,767
High Engineering Channel 1
INT
8,191
-32,768 to 32,767
Low Limit Channel 1
INT
-32,768
-32,768 to 32,767
High Limit Channel 1
INT
32,767
-32,768 to 32,767
Range Type Channel 1
SINT
0
0=4-20mA
2=0-20mA
Fault Mode Channel 1
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value