beautypg.com

Change configuration data – Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 55

background image

Publication 1734-UM008B-EN-P - August 2005

Configure the Adapter 4-25

In this example, the 1734-ACNR adapter is using 2 rack optimized
connections. Slot 1 is a 1734-OB2E module and slot 2 is a 1734-IB2
module, with both modules installed and operating correctly with
0=no error and 1=connection error (typically, module
removed/missing).

Change Configuration Data

One way to change the configuration data for a POINT I/O module:

1. Enter the new configuration data into the controller tags.

2. Select Module or Adapter in the I/O configuration tree.

3. Right-click Properties.

4. Select Properties.

5. Click on the Connection tab.

6. Check the Inhibit Module checkbox.

IMPORTANT

When your first add an I/O module to the I/O
configuration, the default parameters are assigned.
To change these default values, you must modify the
controller reference tags associated with the I/O
module. To download the new configuration, you
must re-initiate the connection to the I/O module.
This download is best achieved by inhibiting and
uninhibiting the module.