Charging and discharging, Operating temperature, Charging and discharging operating temperature – Rockwell Automation 1748 DataSite Configured Panel Installation Instructions User Manual
Page 46: Datasite configured panel battery
Publication 1748-IN001B-EN-P - May 2009
46 DataSite Configured Panel Battery
Charging and Discharging
The batteries supplied with the DataSite configured panel are designed for
discharge in temperatures ranging from -40 °C to 60 °C (-40 °F to 140 °F) and
to be charged in temperatures ranging from -20 °C to 50 °C (-4 °F to 122 °F).
Charging or discharging of these batteries outside of the specified ranges can
cause reduced battery life.
Operating Temperature
When installing the DataSite configured panel in regions where the ambient
temperature could fall below 16 °C (60.8 °F), derating the DataSite configured
panel backup time is necessary to ensure reliable use of the system. The battery
capacity of the DataSite configured panel should be derated as the temperature
decreases.
DataSite Configured Panel Battery Derating
, for derated hours
of backup based on ambient temperature. This table assumes the battery can
be charged to 100% capacity. For details on battery capacity, see
Recommended Battery Replacement Schedule on page 31
DataSite Configured Panel Battery Derating
Average summer
temperature
Maximum duration without sunlight
14 Ah battery
28 Ah battery
56 Ah battery
-40 °C (-40 °F)
8 hours
16 hours
32 hours
-30 °C (-22 °F)
11 hours
22 hours
45 hours
-20 °C (-4 °F)
14 hours
28 hours
57 hours
-10 °C (14 °F)
18 hours
36 hours
72 hours
0 °C (32 °F)
21 hours
42 hours
84 hours
10 °C (50 °F)
23 hours
46 hours
92 hours
20 °C (68 °F)
24 hours
48 hours
97 hours
30 °C (86 °F)
25 hours
50 hours
101 hours
40 °C (104 °F)
25 hours
51 hours
103 hours
50 °C (122 °F)
26 hours
52 hours
105 hours
60 °C (140 °F)
26 hours
52 hours
105 hours
70 °C (158 °F)
26 hours
52 hours
105 hours