Chapter 5, Maintaining the datasite configured panel, Maintenance checklist – Rockwell Automation 1748 DataSite Configured Panel Installation Instructions User Manual
Page 29: Chapter
29
Publication 1748-IN001B-EN-P - May 2009
Chapter
5
Maintaining the DataSite Configured Panel
A periodic maintenance program should be established for the DataSite
configured panel to avoid unnecessary downtime. The frequency of service to
your DataSite configured panel will depend upon the equipment usage and the
environment in which it operates. The following is a suggested checklist and
can be used to establish a maintenance program.
Maintenance Checklist
Use this checklist to perform maintenance on the DataSite configured panel.
1. Inspect the DataSite configured panel once per year or per established
maintenance program.
2. Carefully inspect the door and enclosure sides for evidence of excessive
heat.
3. Check for moisture or any signs of dampness or drippings inside the
DataSite configured panel. Condensation in the conduit or dripping
from an outside source is a common cause of failure. Eliminate any
source of moisture.
a. Seal off conduit, cracks and openings that have allowed and/or could
allow moisture to enter the DataSite configured panel enclosure.
b. Dry or replace and clean insulating material that is damp or wet or
shows signs of moisture.
c. Check devices for wetness or signs of moisture, corrosion or
contamination.
d. Replace damaged or malfunctioning parts.
e. Make sure the source or cause of wetness or moisture contamination
is identified and eliminated.
ATTENTION
De-energize the DataSite configured panel before servicing.