Maintaining the DataSite Configured Panel 31
Battery intervals may vary with the addition of external loads to the
system or rapid changes in ambient temperature. Periodic maintenance
and measurement of battery life should be done to ensure system
reliability.
10. Check all fuses. If replacing fuses, install the same type and rated fuse
that was originally furnished with the DataSite configured panel.
11. Remove accumulated dust and dirt from structure and individual units
by vacuuming. Do not use compressed air, as it may contain moisture
and blow debris within the enclosure.
12. Refer to individual user policies, NFPA 70B, Recommended Practice for
Electrical Equipment Maintenance for Servicing Guidelines.
This table was developed with the assumption that batteries are maintained
properly without additional loads connected to system. Replacement schedules
for additional loads may vary depending on size of load connected. Also, this
table is based on temperature only as the load on the battery will only affect
the battery life if the load is greater than or equal to 1 W continuous.
Recommended Battery Replacement Schedule
Average summer
temperature
Suggested battery replacement intervals
14 Ah battery
28 Ah battery
56 Ah battery
-40 °C (-40 °F)
Not recommended
Not recommended
1.25 years
-30 °C (-22 °F)
Not recommended
9 months
2 years
-20 °C (-4 °F)
Not recommended
1 year
3 years
-10 °C (14 °F)
6 months
1.5 years
3 years
0 °C (32 °F)
9 months
2.25 years
3 years
10 °C (50 °F)
9 months
2.25 years
3.5 years
20 °C (68 °F)
9 months
2.5 years
3.5 years
30 °C (86 °F)
1 year
2.5 years
2.5 years
40 °C (104 °F)
1 year
1.5 years
1.5 years
50 °C (122 °F)
9 months
9 months
9 months
60 °C (140 °F)
6 months
6 months
6 months
70 °C (158 °F)
3 months
3 months
3 months