When using shielded cable wire, ground the foil shield and drain
wire only at one end of the cable. We recommend that you wrap the
foil shield and drain wire together, and connect them to a chassis
mounting bolt, grounding stud or chassis single-point grounding
point (Figure 2.5). Use heat shrink tubing to seal the exit point of the
wires. At the opposite end of the cable, tape exposed shield and drain
wire with electrical tape to insulate it from electrical contact.
Figure 2.5
Cable Grounding
Remove a length of cable
jacket from the Belden 8761
cable.
Pull the foil shield and bare
drain wire from the insulated
wires.
Bare drain
wire
Insulated
wires
Foil
shield
Twist the foil shield and drain
wire together to form a single
strand.
Attach a ground lug, and apply
heat shrink tubing to the exit area.
20104
Belden 8761 Cable
Length as needed
19480
When you connect grounding conductors to the I/O chassis
grounding stud, place a star washer under the first lug, then
place a nut with captive lock washer on top of each ground lug.
Grounding Stud
1
Use the cup washer if crimpĆon lugs are not used.
Chassis Ground
Ground Lug
Ground Lug
1
Star
Washer
I/O Chassis
Side Plate
Nut and Captive
Washer
ExternalĆtooth
Washers
#10 ThreadĆforming screw
19923
Shield and Drain
twisted together
Shield and Drain
twisted together
SingleĆpoint Grounding
Extend shield to termination point.
Expose just enough cable to adequately
terminate inner conductors.
Use heat shrink tubing or
other suitable insulation
where wire exits cable
jacket.
Nut
Refer to Wiring and Grounding Guidelines, publication 1770Ć4.1 for additional
information.