beautypg.com

Adapter input status word – Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 78

background image

Publication 1794-6.5.8 - January 2010

78 Communication and I/O Image Table Mapping with the DeviceNet/ControlNet Adapter

Adapter Input Status Word

The input status word consists of:

I/O module fault bits – 1 status bit for each slot

node address changed – 1 bit

I/O status – 1 bit

The adapter input status word bit descriptions are shown in the fol-

lowing table.

Possible causes for an I/O Module Fault are:

transmission errors on the FLEX I/O backplane

a failed module

a module removed from its terminal base

incorrect module inserted in a slot position

the slot is empty

The node address changed bit is set when the node address switch
setting has been changed since power up. The new node address
does not take affect until the adapter has been powered down and
then powered back up.

15

Bit:

0

1

2

3

4

5

6

7

8

10 through 15

I/O Module Fault Bits

Node Address Changed Bit

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

9

I/O State Bit

Not Used

Bit Description

Bit

Explanation

I/O Module Faults

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node Address Changed

8

This bit is set (1) when the node address switch setting has been
changed sing power up.

I/O State

9

Bit = 0 – idle
Bit = 1 – run

10 thru 15

Not used – sent as zeroes.