Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual
Page 71
Publication 1794-6.5.8 - January 2010
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 71
1
0
1
0
0–10V
binary
0% Under, 2%
Over
0000–F9C2>
0000–63938>
2.5ms
2.5ms
1
0
1
1
0–5V
binary
0% Under, 4%
Over
0000–F3CF>
0000–62415>
2.5ms
2.5ms
1
1
0
0
±20mA
offset binary, 8000H =
0mA
4% Under, 4%
Over
<0618–F9E8>
<1560–63976>
2.5ms
2.5ms
1
1
0
1
4–20mA
offset binary, 8000H =
4mA
4% Under, 4%
Over
<8000–F878>
<32768–63608> 7.5ms
5.0ms
1
1
1
0
±10V
offset binary, 8000H =
0V
2% Under, 2%
Over
<031F–FCE1>
<799–64737>
2.5ms
2.5ms
1
1
1
1
±5V
offset binary, 8000H =
0V
4% Under, 4%
Over
<0618–F9E8>
<1560–63976>
2.5ms
2.5ms
(1)
Underrange for 4-20mA occurs in the blind area below 0 (3.2mA).
(2)
< and > indicate the overrun beyond actual range (about 5%).
Table 4.15
Configuring Your Input Channels
Table 4.16
Setting the Input Filter
Bits
Channel
03
02
01
00
Input Channel 0
07
06
05
04
Input Channel 1
A/D Conversion
Rate
Low Pass Filter
0
0
0
0
1200Hz
No low pass
0
0
0
1
1200Hz
100ms low pass
0
0
1
0
1200Hz
500ms low pass
0
0
1
1
1200Hz
1000ms low pass
0
1
0
0
600Hz
No low pass
0
1
0
1
600Hz
100ms low pass
0
1
1
0
600Hz
500ms low pass
0
1
1
1
600Hz
1000ms low pass
1
0
0
0
300Hz
No low pass
1
0
0
1
300Hz
100ms low pass
1
0
1
0
300Hz
500ms low pass
1
0
1
1
300Hz
1000ms low pass
1
1
0
0
150Hz
No low pass
1
1
0
1
150Hz
100ms low pass
1
1
1
0
150Hz
500ms low pass
1
1
1
1
150Hz
1000ms low pass