Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual
Page 125

Publication 1794-6.5.8 - January 2010
Calibrating Your Module 123
5. Send another BTW to the module to reset the CK bit (0). When
the GO bit is low, the previously determined offset coefficients
are stored in EEPROM for the selected channels. If QK is set (1)
high, the same coefficients will be stored to all “like”
configurations (i.e. if configuration bits are set for a specific
voltage, both unipolar/bipolar, x1/x2 – will have the same
coefficients stored – see Table 7.1). If calibrate for 0-20mA
current range, 4-20mA range channels are also automatically
calibrated.
6. Monitor the module block transfer read word. Clear the IC bit to
0, and offset calibration is terminated.
Table 7.1
Configuration
Nominal Range
Data Type
Comments
4
0–20mA
signed 2’s complement
%
If you calibrate any of
this group, the rest of
the group will also be
calibrated.
8
0–20mA
binary
C
±20mA
offset binary
6
0–10V
signed 2’s complement
%
If you calibrate any of
this group, the rest of
the group will also be
calibrated.
A
0–10V
binary
B
0–5V
binary
2
±10V
signed 2’s complement
If you calibrate any of
this group, the rest of
the group will also be
calibrated.
7
±10V
signed 2’s complement
%
E
±10V
offset binary
3
±5V
signed 2’s complement
If you calibrate any of
this group, the rest of
the group will also be
calibrated.
F
±5V
offset binary
1
4–20mA
signed 2’s complement
If you calibrate 0-20mA
range, all 4- mA g s are
calibrated.
5
4-20mA
signed 2’s complement
%
9
4–20mA
binary
D
4–20mA
offset binary